YouTube Facebook Twitter Recommend on Google+
Corporate Swoosh
QwikSEER+
HVAC Org Memberships
New Reference Books
Product Image
QT2510
QwikInjector®

Add oil or other liquid additives into a vapor-compression refrigeration or air conditioning system quickly and without interrupting operation of the system. QwikInjector® uses the natural pressure difference developed by the compressor of an operating system to push any liquid additive into a system.

Anytime a liquid product specifies that it needs to be introduced into an operating system QwikInjector® can be used as the injection medium. QwikShot® Acid Flush™, dyes, and oil additives are all common items that require an injection tool to use. Our injection tool is intentionally sized for very small doses so that customers won't accidently add non-condensables into a system.

Articles of Interest Related to this Product

QwikShot Video QwikShot® (QT2500) - Acid Treatment with Warranty
QwikShot FAQ Video QwikShot® (QT2500) - Frequently Asked Questions
Online Article Refrigerant Acids and Their Treatment
Online Article Preventative Maintenance of HVAC/R Systems:
Fix the Problem, Don't Treat the Symptoms
Online Article A Discussion of Acids in Refrigeration Systems
Online Article Don't Treat Today's Refrigeration Systems
with Yesterday's Techniques
  1. Unscrew QwikInjector® top and fill with liquid additive, such as QwikShot. *Fill completely to ensure air does not get trapped in vessel

    Connect the QwickInjector® as Shown in the Illustrations Below.

    It is desirable to have liquid overflow over the edges. The overflow indicates that there is no excess air within the Injector.

  2. Connect to the low side of the operating system FIRST.
  3. Connect to the high side of the operating system LAST.
  4. Open the valve on the manifold. The high side pressure will push the liquid into the low side of the system.
Injector Instructions

CAUTIONS

  • Maximum Working Pressure is 500psig.
  • Never leave QwikInjector® connected to the hoses. After use, always disconnect and disassemble.
  • Depress the valve core to relieve pressure prior to unscrewing cap.
  • Store the QwickInjector® with the cap loose to prevent thread binding and pressure build-up.

CLICK BELOW
TO REQUEST INFORMATION